lib-modbus 库参考
原文: https://finproducts.atlassian.net/wiki/spaces/JIDD3/pages/34793750634/FIN+5.3.1+lib-modbus 中文整理基于 FIN 5.3.1
导读: 本页为
lib-modbus的 API / 标签 / 函数参考文档。
以下为 API 参考,保留英文以便对照源码;目录已列出(英文标题便于检索);概述已尽量中译。
目录(导读)
- lib
- meta
- docs
- tags
- funcs
- views
- Overview
- Supported Protocols
- TCP/IP
- RTU over TCP/IP
- Register Map
- Addressing
- Ping
- Data Type
- Read/Write
- Scale Factor
- Dis, Unit, Tags
- Current Points
- Writable Points
- History
- Block Reads
- modbusBlockGap
- modbusBlockMax
- def
- modbusLearn(conn, arg: null)
- modbusPing(conn)
- modbusRead(conn, regs)
- modbusRegMap(name)
- modbusRegMaps()
- modbusSyncCur(points)
- modbusWrite(conn, reg, val)
概述(中译)
Modbus 连接器
API 正文(英文)
docs
Overview • Supported Protocols • Register Map • Current Points • Writable Points • History • Block Reads
tags
| modbusBlockGap | Applied to modbusConn to allow for gaps in block reads |
| modbusBlockMax | Applied to modbusConn to limit the maximum number of registers to read in a block read |
| modbusConn | Modbus connector |
| modbusConnRef | Used on a proxy point to reference its parent modbusConn |
| modbusCur | Modbus address to use for current value subscriptions |
| modbusPoint | Point which synchronizes data via a Haystack connector |
| modbusReadTimeout | How long to wait before timing out on a modbus read |
| modbusRegMapUri | Applied to modbusConn to define the register map CSV file |
| modbusSlave | Applied to modbusConn to identify the slave address on this modbus network |
| modbusWrite | Used on a modbus proxy point to store the id of the entity in the remote system used to write writeVal |
| modbusWriteTimeout | How long to wait before timing out on a modbus write |
funcs
| modbusLearn | Deprecated - use connLearn() |
| modbusPing | Deprecated - use connPing() |
| modbusRead | Read a point value for given register name on connector instance |
| modbusRegMap | Return given register map contents |
| modbusRegMaps | List installed register maps including source |
| modbusSyncCur | Deprecated - use connSyncCur() |
| modbusWrite | Write a value to given register name on connecter instance |
views
| modbusRegMap | Manage Modbus register map files |
lib modbus
Overview
The ModbusExt implements connector support for Modbus protocol.
Supported Protocols
ModbusExt supports two protocols for accessing Modbus slave devices:
TCP/IP
To setup a connector to access a Modbus slave over TCP/IP, we use the modbus-tcp URI scheme:
dis: "Modbus TCP/IP Connector"
conn
modbusConn
uri: `modbus-tcp://host/`
modbusSlave: 1
modbusRegMapUri: `data/modbus/xxx.csv`RTU over TCP/IP
To access the slave using serial RTU over a TCP connection, use the modbus-rtutcp scheme:
dis: "Modbus RTU over TCP/IP Connector"
conn
modbusConn
uri: `modbus-rtutcp://host/`
modbusSlave: 1
modbusRegMapUri: `data/modbus/xxx.csv`Register Map
Modbus connectors are required to define a register map using the modbusRegMapUri tag. The register map specifies which points get read/written out of a Modbus slave. The register map URI must be a path relative to the project's home directory or can be a fan:// URI to a CSV file bundled in a pod.
Register maps are simple CSV files:
name, addr, data, rw, scale, dis, unit, tags
ping, 40001, u2, r, , Ping, ,
do0, 00017, bit, rw, , DO-0, ,
do1, 00017, bit, rw, , DO-1, ,
ai0, 40001, u2, r, , AI-0, ,
ai1, 40002, u2, r, *10, AI-1, kW, powerAddressing
Register address are defined with addr column and specified using Modbus convention:
0xxxx Coil 00001-065536
1xxxx Discrete Input 10001-165536
3xxxx Input Register 30001-365536
4xxxx Holding Register 40001-465536Ping
A valid ping register is required in order to test connectivity to slave.
Data Type
The data column specifies how register data is modeled.
bit Bool
u1 Unsigned 8-bit Int
u2 Unsigned 16-bit Int
u4 Unsigned 32-bit Int
s1 Signed 8-bit Int
s2 Signed 16-bit Int
s4 Signed 32-bit Int
s8 Signed 64-bit Int
f4 32-bit Float
f8 64-bit FloatBit Mask
The bit data type supports a position notation for cases where bits are packed into input or holding registers:
name, addr, data, rw
do0, 40101, bit:0, rw
do1, 40101, bit:1, rw
do2, 40101, bit:2, rwWord and Byte Order
If register data is not stored in network byte order, you can specify the order using a suffix:
u2le Unsigned 16-bit Int Little endian byte and word order
u2leb Unsigned 16-bit Int Little endian byte order only
u2lew Unsigned 16-bit Int Little endian word order onlyRead/Write
Read and write permissions are configured using rw column:
rw Register may be read and written
r Register is read-only
w Register is write-onlyScale Factor
An optional scale factor can be applied to registers using the scale column. The scale format is [op] [num] where the factor is a numeric constant.
add: +1.5
minus: -0.25
mult: *10
div: /1000Dis, Unit, Tags
The dis, unit, and tags column allow optional pre-configuration for the point during the learn process:
name, addr, data, rw, dis, unit, tags
ai1, 40002, u2, r, AI-1, kW, power foo barCurrent Points
Modbus proxy points are configured with modbusCur tag, which maps to a valid register map name:
point
modbusConnRef: @conn
modbusCur: ai0Writable Points
Modbus proxy points are configured to write to remote system points via the modbusWrite tag:
point
writable
modbusConnRef: @conn
modbusWrite: ao5History
History synchronization is not supported by Modbus. You will need to use collection to store history.
Block Reads
Modbus connectors will attempt to optimize consecutive registers into a single block read when possible. This behavior can be tuned by adding the modbusBlockGap and modbusBlockMax tags to your modbusConn rec, or by configuring them on the connector's associated conn tuning rec.
modbusBlockGap
By default, blocks require all points to be in truly consecutive registers:
// block 1
40001 u2
40002 u2
40003 u2
// block 2
40005 u2If you have a small gap in an otherwise sequential run of registers, you can tune to maintain a single read by adding the modbusBlockGap tag to your conn rec. This tag specifies the maximum number of registers that can be skipped for a single block:
modbusConn
modbusBlockGap: 1
// block 1
40001 u2
40002 u2
40003 u2
40005 u2 // 400004 will be read but discardedmodbusBlockMax
By default, blocks are limited to 100 total registers (which includes skipped registers from modbusBlockGap). To force a connector to split blocks into smaller or larger chunks, add the modbusBlockMax tag to your conn rec:
modbusConn
modbusBlockMax: 2
// block 1
40001 u2
40002 u2
// block 2
40003 u2
40004 u2Be aware a block read failure will result in the entire block's points being marked as fault.
def
func:modbusLearn
modbusLearn(conn, arg: null)
Deprecated - use connLearn()
meta
| admin | ✓ |
| def | func:modbusLearn |
| deprecated | ✓ |
| is | func |
| lib | lib:modbus |
| name | modbusLearn |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
func:modbusPing
modbusPing(conn)
Deprecated - use connPing()
meta
| admin | ✓ |
| def | func:modbusPing |
| deprecated | ✓ |
| is | func |
| lib | lib:modbus |
| name | modbusPing |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
func:modbusRead
modbusRead(conn, regs)
Read a point value for given register name on connector instance. The regs argument may be a single Str name, or a Str[] for a block read. The grid returned will contain a row for each register requested and two columns: name and val.
meta
| admin | ✓ |
| def | func:modbusRead |
| is | func |
| lib | lib:modbus |
| name | modbusRead |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
func:modbusRegMap
modbusRegMap(name)
Return given register map contents. Do not include the file extension in the name.
modbusRegMap("myRegisterMap")
meta
| def | func:modbusRegMap |
| is | func |
| lib | lib:modbus |
| name | modbusRegMap |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
func:modbusRegMaps
modbusRegMaps()
List installed register maps including source.
meta
| def | func:modbusRegMaps |
| is | func |
| lib | lib:modbus |
| name | modbusRegMaps |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
func:modbusSyncCur
modbusSyncCur(points)
Deprecated - use connSyncCur()
meta
| admin | ✓ |
| def | func:modbusSyncCur |
| deprecated | ✓ |
| is | func |
| lib | lib:modbus |
| name | modbusSyncCur |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
func:modbusWrite
modbusWrite(conn, reg, val)
Write a value to given register name on connecter instance.
meta
| admin | ✓ |
| def | func:modbusWrite |
| is | func |
| lib | lib:modbus |
| name | modbusWrite |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| func | Axon function |
def
modbusBlockGap
Applied to modbusConn to allow for gaps in block reads. See modbus for more information.
meta
| def | modbusBlockGap |
| is | int |
| lib | lib:modbus |
| tagOn | modbusConn |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| number | Integer or floating point numbers annotated with an optional unit |
| int | Unitless integer number |
def
modbusBlockMax
Applied to modbusConn to limit the maximum number of registers to read in a block read. See modbus for more information.
meta
| def | modbusBlockMax |
| is | int |
| lib | lib:modbus |
| tagOn | modbusConn |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| number | Integer or floating point numbers annotated with an optional unit |
| int | Unitless integer number |
def
modbusConn
Modbus connector
meta
| connFeatures | |
| def | modbusConn |
| icon | modbus |
| is | conn |
| lib | lib:modbus |
usage
| modbusConn conn |
supertypes
| marker | Marker labels a dict with typing information |
| entity | Top-level dicts with a unique identifier |
| conn | Connector for communication to a remote system |
tags
| actorTimeout | Timeout for messages send to the connector's actor thread |
| connErr | Error message associated when connStatus indicates an error condition |
| connLinger | Linger timeout used to keep a connector open |
| connOpenRetryFreq | Duration used for connector open retries |
| connPingFreq | Duration used to configure the auto-ping feature on a given connector |
| connState | Current connection state of a connector as one of the predefined strings |
| connStatus | Current status of a connector as one of the predefined strings See Connectors |
| connTuningRef | Reference to a tuning configuration defined by a connTuning rec |
| dis | Display name for an entity |
| disabled | Indicates the entity is in a disabled state |
| id | Defines the unique identifier of an entity in system using a ref value type |
| modbusBlockGap | Applied to modbusConn to allow for gaps in block reads |
| modbusBlockMax | Applied to modbusConn to limit the maximum number of registers to read in a block read |
| modbusReadTimeout | How long to wait before timing out on a modbus read |
| modbusRegMapUri | Applied to modbusConn to define the register map CSV file |
| modbusSlave | Applied to modbusConn to identify the slave address on this modbus network |
| modbusWriteTimeout | How long to wait before timing out on a modbus write |
| uri | Universal resource identifier |
def
modbusConnRef
Used on a proxy point to reference its parent modbusConn
meta
| def | modbusConnRef |
| is | ref |
| lib | lib:modbus |
| of | modbusConn |
| tagOn | modbusPoint |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| ref | Reference to an entity |
def
modbusCur
Modbus address to use for current value subscriptions. See modbus for format.
meta
| def | modbusCur |
| is | str |
| lib | lib:modbus |
| tagOn | modbusPoint |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| str | Unicode string of characters |
def
modbusPoint
Point which synchronizes data via a Haystack connector.
meta
| def | modbusPoint |
| is | connPoint |
| lib | lib:modbus |
usage
| modbusPoint point |
supertypes
| marker | Marker labels a dict with typing information |
| entity | Top-level dicts with a unique identifier |
| point | Data point such as a sensor or actuator |
| connPoint | Point associated with a connector for data synchronization with a remote system |
tags
| connTuningRef | Reference to a tuning configuration defined by a connTuning rec |
| cur | Supports current value |
| curCalibration | Calibration value to apply to adjust the value read from the connector before updating curVal |
| curConvert | Conversion to apply when reading curVal from connector |
| dis | Display name for an entity |
| disMacro | Display name using macro syntax |
| disabled | Indicates the entity is in a disabled state |
| enum | Defines an eumeration of string key names |
| equipRef | Reference to equip which contains this entity |
| ghgFactorHis | Identifies point record with interval emission factor data that the Greenhouse Gas Emission Engine uses to calculate emissions |
| his | Supports historization of data |
| hisConvert | Conversion to apply when reading history data from connector |
| id | Defines the unique identifier of an entity in system using a ref value type |
| kind | Kind name used to identity a value data type |
| maxVal | Inclusive maximum for a numeric value |
| minVal | Inclusive minimum for a numeric value |
| modbusConnRef | Used on a proxy point to reference its parent modbusConn |
| modbusCur | Modbus address to use for current value subscriptions |
| modbusWrite | Used on a modbus proxy point to store the id of the entity in the remote system used to write writeVal |
| navName | Navigation name commonly used with disMacro to create computed display strings |
| pointFunction | Classifies the point as a sensor, command, or setpoint |
| pointQuantity | Quantity the point senses or controls |
| pointSubject | What the point senses or controls |
| siteRef | Reference to site which contains the entity |
| spaceRef | Reference to space which contains this entity |
| systemRef | Reference to system |
| tz | Timezone identifier from standard timezone database |
| unit | Unit identifier from standard unit database |
| writable | Supports writing data |
| writeConvert | Conversion to apply when writing writeVal to the connector |
def
modbusReadTimeout
How long to wait before timing out on a modbus read.
meta
| def | modbusReadTimeout |
| is | duration |
| lib | lib:modbus |
| tagOn | modbusConn |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| number | Integer or floating point numbers annotated with an optional unit |
| duration | Number with a unit of time |
def
modbusRegMapUri
Applied to modbusConn to define the register map CSV file. This URI must be a path relative to the project's home directory or can be a "fan://" URI to a CSV file bundled in a pod.
meta
| def | modbusRegMapUri |
| is | uri |
| lib | lib:modbus |
| tagOn | modbusConn |
| uiInput | modbusExt::ModbusRegMapInput |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| uri | Universal resource identifier |
def
modbusSlave
Applied to modbusConn to identify the slave address on this modbus network.
meta
| def | modbusSlave |
| is | int |
| lib | lib:modbus |
| tagOn | modbusConn |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| number | Integer or floating point numbers annotated with an optional unit |
| int | Unitless integer number |
def
modbusWrite
Used on a modbus proxy point to store the id of the entity in the remote system used to write writeVal. See modbus for format.
meta
| def | modbusWrite |
| is | str |
| lib | lib:modbus |
| tagOn | modbusPoint |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| str | Unicode string of characters |
def
modbusWriteTimeout
How long to wait before timing out on a modbus write.
meta
| def | modbusWriteTimeout |
| is | duration |
| lib | lib:modbus |
| tagOn | modbusConn |
supertypes
| val | Data value type |
| scalar | Scalar is an atomic value kind |
| number | Integer or floating point numbers annotated with an optional unit |
| duration | Number with a unit of time |
def
view:modbusRegMap
Manage Modbus register map files
meta
| admin | ✓ |
| appName | conn |
| def | view:modbusRegMap |
| disKey | ui::regMap |
| icon | view |
| is | view |
| lib | lib:modbus |
supertypes
| feature | Feature namespace of definitions formatted as feature:name |
| view | Fresco UI view |
src
view: { uiType:"modbusExt::RegMapView" }
data: { expr:"modbusRegMapList()" }